HVAC > HVAC Valves & Accessories > Smart Valves > Tempstar > SV9641M4510
| MFG Number | 0604 |
|---|---|
| Box Quantity | 1 |
| Date Added | 2001-06-29 |
| Replaced By | 097668 |
| RHS Price Page | 05-9A |
| Additional Information | |
|---|---|
| id | 3217 |
| item | 050580 |
| mfgno | 0604 |
| adddate | 2001-06-29 |
| Logo | ICP_logo.tif |
| Control Voltage | 24 Vac |
| Electrical Ratings | 24 Vac |
| Frequency | 60/50 Hz |
| Pressure | |
| Tapping | 1/8 in. - NPT |
| Ratings (psi) | 1/2 psi |
| Ambient Temp Range °F(°C) | -40°F to +175°F(-40°C to +79° C) |
| Body Pattern | Straight-through |
| Cool Fan Off Delay | adj. 30, 60 sec (set at 30 sec) |
| Cool Fan On Delay | adj. 4, 30 sec (set at 4 sec) |
| Dimensions Wide x High x Long (in) | 3.2 x 4.9 x 4.1 |
| Flame Failure Response Time (sec) | 1.6 sec @ 3 µA |
| Flame Sense | Two Rod |
| Heat Fan Off Delay | adj. 60, 120, 150, 180 sec (set at 120 sec) |
| Heat Fan On Delay | adj. 30, 60 sec (set at 30 sec) |
| Ignition Sequence | Intermittent Pilot |
| Ignition Source | Pilot |
| Ignition System Type | Intermittent Hot Surface Pilot Ignition |
| Ignition Trial Time (sec) | 90 sec |
| Ignition Trials To Lockout | continuous retry |
| Includes | Two 3/4 in. x 1/2 in. reducer bushings and an LP conversion kit. |
| Inlet/Outlet Size (in) | 3/4 in. NPT x 3/4 in. NPT. |
| Maximum Capacity (ft³/hr) | 415 ft³/hr |
| Maximum Capacity at 1 in PD (ft³/hr) | 300 ft³/hr |
| Minimum Capacity (ft³/hr) | 30 ft³/hr |
| Opening Characteristics (standard, step) | Standard Opening |
| Post Purge | 30 seconds |
| PrePurge | 15 seconds |
| Pressure Regulator Setting (psi) | 3.5 in. wc |
Features:
· Communicates directly with an electronic fan timer (ST9160 Electronic Fan Timer for single stage applications; ST9162 Electronic Fan Timer for two-stage applications) in typical forced warm air furnace applications.
· Also interfaces with the 208907 Terminal Board, providing compatibility with power stealing thermostats. Or, they directly interface with the appropriate power supplies and a system thermostat for additional appliance applications.
· When controlled directly by a thermostat, these controls do not provide a postpurge function, because power to the control is removed when the thermostat call for heat ends.
· The SV9641 Systems are suitable for a wide range of fan-assisted combustion gas-fired appliances including furnaces, rooftop furnaces, boilers, unit heaters, infrared heaters, water heaters and commercial cooking appliances.
· Standard opening and 3.5 in. wc pressure regulator settings
Mounting:
· 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
![]()