HVAC > Controls > Oil Burner Controls > Honeywell > R8184M Series 80 Protectorelay Oil Burner Control
| Additional Information | |
|---|---|
| Logo | Honeywell.tif |
| Ambient Temperature Range | -40°F to +130°F (-40°C to +54°C) |
| Dimension | 4-3/8" H x 4-1/8" W x 2-1/2" D |
| Electrical Rating Full Load @ 120 Vac | 7.4 A |
| Electrical Rating Full Load @ 240 Vac | 3.7 A |
| Electrical Rating Locked Rotor @ 120 Vac | 44.4 A |
| Electrical Rating Locked Rotor @ 240 Vac | 22.2 A |
| Electrical Rating Transformer | 40 VA |
| Frequency | 60 Hz |
| Ignition Rating | 360 VA (in addition to the load relay rating) |
| Ignition Type | Intermittent |
| Mounting Bracket | Mounts on Standard 4" x 4" Junction Box |
| Power Consumption Running | 6.5 A |
| Power Consumption Start | 9.0 A |
| Voltage | |
| Primary | 120 |
| Secondary | 26.5 |
| Safety Switch Timing | 45 sec. |
| Tradeline Value | Tradeline |
Features:
· Ignition is on whenever the burner is on (intermittent ignition-also called constant ignition).
· Solid state flame sensing circuit.
· External button to manually reset safety switch after lockout.
· Enclosed safety switch must be manually reset after safety shutdown.
· R8184M includes 40 VA transformer and Y and G terminals for connection of cooling equipment.
· Mounts on standard 4 x 4 in. junction box.
· C554A Cadmium Sulfide Flame Detector and a 24 Vac thermostat required.
· UL Listed
![]()