| Additional Information | |
|---|---|
| Logo | Honeywell.tif |
| Alarm Load Ratings (Pilot Duty) | 75 VA @ 120/240 Vac, 50-60 Hz; 25 VA @ 24V, 50-60 Hz |
| Alarm Load Ratings (Resistive) | 1.5 A @ 120/240V, 50-60Hz; 3 A @ 24 V, 50-60 Hz |
| Ambient Temperature Range | -40°F to +130°F (-40°C to +54°C) |
| Dimension | 4-3/8" H x 4-1/8" W x 2-1/2" D |
| Electrical Rating Full Load @ 120 Vac | 7.4 A |
| Electrical Rating Full Load @ 240 Vac | 3.7 A |
| Electrical Rating Locked Rotor @ 120 Vac | 44.4 A |
| Electrical Rating Locked Rotor @ 240 Vac | 22.2 A |
| Ignition Type | Intermittent |
| Mounting Bracket | For Mounting on a Standard 4" x 4" Junction Box or Direct Mounting on Burne |
| Safety Switch Timing | 45 sec. |
| Tradeline Value | Tradeline |
Features:
· Controls oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat.
· Solid state flame sensing circuit.
· LED on terminal strip indicates system lockout.
· Remote lockout indication available on some models.
· Enclosed safety switch with external reset button.
· Manual trip lever opens safety switch for system maintenance.
· Mounts on standard 4 x 4 in. junction box; select models may be mounted directly on burner housing.
· C554A Cadmium Sulfide Flame Detector and 24 Vac thermostat required.
· Comments: With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
· UL Listed
· CSA Approved
![]()