HVAC > Controls > Oil Burner Controls > Honeywell > C554 Series Cadmium-Sulfide Flame Detector, For Sequencing Oil Burner Systems
| Additional Information | |
|---|---|
| Logo | Honeywell.tif |
| Ambient Temperature Range | 140°F (60°C) |
| CAD Cells | 130367 High Sensitivity CAD Cell 12 MA Minimum Sensitivity at 2\' Candles |
| Dimension | 1-7/8" H x 1" L x 1/2" W |
| Includes | A, B, E, J and P Mounting Brackets and Fuel Line Adaptor |
| Mounting Bracket | Type R |
| Tradeline Value | Super Tradeline |
| Lead Length | 60" |
| Used With | R4166, R4184, R8182, R8184, R8185, R8404, R8991, R7997 |
Features:
· On flame failure, the light sensitive cadmium sulfide cell, in conjunction with flame sensing circuitry,
causes the Protectorelay control to shutdown the main oil burner.
· Glass-to-metal hermetic seal in plug-in cell prevents deterioration by humidity, soot or oil fumes.
· Cadmium sulfide sensing element provides faster response than bimetal sensors.
· Mounting brackets available to fit all applications, Plug-in cell for easy replacement.
· Recessed cell provides more accurate flame sighting and prevents accumulation of dirt and soot on
cell face, Cadmium Sulfide Flame Detector two-wire, two-piece plug-in cell
· Electrical Connection: NEC Class 1; Includes 2 Flag 1/4" Quick Connects
· Replacement Parts - 120320 Replacement Cad Cell. 7.5 mA minimum sensitivity at 2 ft. candles;
130367 Replacement Cad Cell. 12.0 mA minimum sensitivity at 2 ft. candles.
Electrical:
· Maximum voltage 60 Vdc or 60 Vac peak.
Application:
· Cadmium Sulfide Flame Detector (cad cell) is a photoconductive flame detector
· It consists of a plug-in, light sensitive cell and a socket with factory-installed mounting bracket and leadwire.
· The detector is installed inside the air tube of the burner where the cell can view the flame.
![]()