HVAC > Controls > Ignition Controls & Modules > White Rodgers > Universal Non-Integrated HSI Ignition Module
| MFG Number | 1010 |
|---|---|
| Box Quantity | 20 |
| Date Added | 2003-07-03 |
| Replaced By | |
| RHS Price Page | 57-35 |
| Document | Download Documents\50E47-843 Universal Non-Integrated HSI Ignition Module_D.doc |
|
Features: · Program keys for multiple timing selections. · Tri-colored LED indicator for diagnostics. · Direct and indirect flame sense compatible. · Universal design for maximum versatility. · Surface mount or 4” x 4 junction box Application: · Gas-Fired Non-Integrated · Forced-Air Furnaces and Boilers Electrical Rating: · Input 18 to 30 VAC, 25 VAC nominal · Max. Input Current @ 25 VAC; 200mA @ 25°C Relay Load Settings: · Valve Relay: 1.5 amps @ 25 VAC 60 Hz .6pf · Ignitor Relay: 6.0 amps @ 120 VAC 60 Hz resistive |
Flame Current Requirements: · Min. current to insure flame: 2 µADC · Min. current for non-detection: 0.2 µADC · Max. allowable leakage resistance: 100 M Ohms Kit Includes: · Program Keys · Mounting Hardware · Double-Sided Foam Back Tape (for ease of installation) · Extensive Cross-Reference Guide · Color-Coded Timing Label · Pre-Printed Hanging Carton · Instructions in English/Instrucciones en Espanol |